BY CREANOVA
ENGINEERS…www.creanovaengineers.blogspot.in
TRANSFORMERS FROM
Creanova Engineers…!
The coil on the left has fewer coils than that at right (the insets show
close-ups). To make a step-down transformer, one only has to put the source
on the right and the load on the left. (Important safety note: for a
real transformer, you could only 'plug it in backwards' only after verifying
that the voltage rating were appropriate.) So, how does s transformer work? The core (shaded) has high magnetic permeability (ie a material that forms a magnetic field much more easily than free space does, due to the orientation of atomic dipoles). The result is that the field is concentrated inside the core, and almost no field lines leave the core. If follows that the magnetic flux φ through the primary and secondary are equal, as shown. From Faraday's law, the emf in each turn, whether in the primary or secondary coil, is −dφ/dt. If we neglect resistance and other losses in the transformer, the terminal voltage equals the emf. For the Np turns of the primary, this gives
Vp = − Np.dφ/dt
.
For the Ns turns of the secondary, this
gives
Vs = − Ns.φ/dt
Dividing these equations gives the transformer
equation
Vs/Vp
= Ns/Np = r.
where r is the turns ratio. What about the
current? If we neglect losses in the transformer (see the section below on
efficiency), and if we assume that the voltage and current have similar phase
relationships in the primary and secondary, then from conservation of energy
we may write, in steady state:
Power in = power out,
so
VpIp = VsIs,
whence
Is/Ip = Np/Ns
= 1/r.
So you don't get something for nothing: if you
increase the voltage, you decrease the current by at least the same factor.
Note that, in the photograph, the coil with more turns has thinner wire,
because it is designed to carry less current than that with fewer turns.
In some cases, decreasing the current is the aim of the exercise. In power
transmission lines, for example, the power lost in heating the wires due to
their non-zero resistance is proportional to the square of the current. So it
saves a lot of energy to transmit the electrical power from power station to
city at very high voltages so that the currents are only modest. |
Finally, and again assuming that the transformer is
ideal, let's ask what the resistor in the secondary circuit 'looks like' to the
primary circuit. In the primary circuit:
Vp = Vs/r
and
Ip = Is.r
so
Vp/Ip = Vs/r2Is
= R/r2.
R/r2 is called the reflected
resistance. Provided that the frequency is not too high, and provided that
there is a load resistance (conditions usually met in practical transformers), the
inductive reactance of the primary is much smaller than this reflected
resistance, so the primary circuit behaves as though the source were driving a
resistor of value R/r2. This allows transformers to be used as impedance
matchers. A load with low input impedance can be matched to circuit with
high output impedance using a step down transformer.
We have been asked: how
does the transformer equation fit with Ohm's law? If the secondary voltage is
twice the primary, why isn't the secondary current twice the primary? First,
one can only apply Ohm's law to resistors and, if there were (only) a resistor
on both primary and secondary sides, then the voltage on both sides would be
zero. Usually, the primary coil is connected to an AC source, which does not obey
Ohm's law. For instance, the mains supply is 240 volts if the current is zero,
and not far from 240 volts if the current is 1 amp.
EFFICIENCY OF TRANSFORMERS
In practice, real transformers are less than 100%
efficient.
- First, there are resistive losses in the coils (losing power I2.r). For a given material, the resistance of the coils can be reduced by making their cross section large. The resistivity can also be made low by using high purity copper. (See Drift velocity and Ohm's law.)
- Second, there are some eddy current losses in the core. These can be reduced by laminating the core. Laminations reduce the area of circuits in the core, and so reduce the Faraday emf, and so the current flowing in the core, and so the energy thus lost.
- Third, there are hysteresis losses in the core. The magentisation and demagnetisation curves for magnetic materials are often a little different (hysteresis or history depedence) and this means that the energy required to magnetise the core (while the current is increasing) is not entirely recovered during demagnetisation. The difference in energy is lost as heat in the core.
- Finally, the geometric design as well as the material of the core may be optimised to ensure that the magnetic flux in each coil of the secondary is nearly the same as that in each coil of the primary.
MORE ABOUT TRANSFORMERS: AC VS DC GENERATORS
Transformers
only work on AC, which is one of the great advantages of AC. Transformers allow
240V to be stepped down to convenient levels for digital electronics (only a
few volts) or for other low power applications (typically 12V). Transformers
step the voltage up for transmission, as mentioned above, and down for safe
distribution. Without transformers, the waste of electric power in distribution
networks, already high, would be enormous. It is possible to convert voltages
in DC, but more complicated than with AC. Further, such conversions are often
inefficient and/or expensive. AC has the further advantage that it can be used
on AC motors, which are usually preferable to DC motors for high power
applications.